2016-02-09 12:01:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1. PROVIDE INFORMATION REGARDING THE SYSTEM DESIGN |
| TYPE, DESIGN CRITERIA AND CALCULATIONS, |
| EQUIPMENTLISTING IN COMPLIANCE WITH, NFPA 92, STANDARD |
| FOR SMOKE CONTROL SYSTEMS. |
| |
| 2. THE SYSTEM DESIGN SHALL PROVIDE NOTES, INDICATIONS |
| AND INFORMATION COMPLYING WITH NFPA 101, CHAPTER 9 |
| BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT, |
| INCLUDING BUT NOT LIMITED TO, |
| |
| 9.3 SMOKE CONTROL. |
| 9.3.1 WHERE REQUIRED BY THE PROVISIONS OF ANOTHER |
| SECTION OF THIS |
| CODE, SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, |
| INSPECTED, TESTED, |
| AND MAINTAINED IN ACCORDANCE WITH NFPA 92, STANDARD FOR |
| SMOKE |
| CONTROL SYSTEMS; NFPA 204, STANDARD FOR SMOKE AND HEAT |
| VENTING; OR NATIONALLY RECOGNIZED STANDARDS, |
| ENGINEERING GUIDES, |
| OR RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY |
| HAVING |
| JURISDICTION. |
| 9.3.2 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE |
| INTENT OF |
| THE SYSTEM, THE DESIGN METHOD USED, THE APPROPRIATENESS |
| OF THE |
| METHOD USED, AND THE REQUIRED MEANS OF INSPECTING, |
| TESTING, AND |
| MAINTAINING THE SYSTEM. |
| 9.3.3 ACCEPTANCE TESTING SHALL BE PERFORMED BY A |
| SPECIAL |
| INSPECTOR IN ACCORDANCE WITH SECTION 9.9. |
| 9.3.4 SMOKE CONTROL SYSTEM OPERATION. |
| 9.3.4.1 FLOOR- OR ZONE-DEPENDENT SMOKE CONTROL SYSTEMS |
| SHALL BE |
| AUTOMATICALLY ACTIVATED BY SPRINKLER WATERFLOW OR SMOKE |
| DETECTION |
| SYSTEMS. |
| 9.3.4.2 MEANS FOR MANUAL OPERATION OF SMOKE CONTROL |
| SYSTEMS |
| SHALL BE PROVIDED AT AN APPROVED LOCATION. |
| |
| 3. ADDITIONAL, COMMNETS MAY BE PROVIDED WITH THE |
| RE-SUBMITTAL OF THE ABOVE REQUIREMENTS. |
| |
| PETER LEDUC |
| FIRE MARSHAL |