Plan Review Notes
Plan Review Notes For Permit 16020105
Permit Number 16020105
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-02-09 12:01:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE INFORMATION REGARDING THE SYSTEM DESIGN
 TYPE, DESIGN CRITERIA AND CALCULATIONS,
 EQUIPMENTLISTING IN COMPLIANCE WITH, NFPA 92, STANDARD
 FOR SMOKE CONTROL SYSTEMS.
  
 2. THE SYSTEM DESIGN SHALL PROVIDE NOTES, INDICATIONS
 AND INFORMATION COMPLYING WITH NFPA 101, CHAPTER 9
 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT,
 INCLUDING BUT NOT LIMITED TO,
  
 9.3 SMOKE CONTROL.
 9.3.1 WHERE REQUIRED BY THE PROVISIONS OF ANOTHER
 SECTION OF THIS
 CODE, SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED,
 AND MAINTAINED IN ACCORDANCE WITH NFPA 92, STANDARD FOR
 SMOKE
 CONTROL SYSTEMS; NFPA 204, STANDARD FOR SMOKE AND HEAT
 VENTING; OR NATIONALLY RECOGNIZED STANDARDS,
 ENGINEERING GUIDES,
 OR RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING
 JURISDICTION.
 9.3.2 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF
 THE SYSTEM, THE DESIGN METHOD USED, THE APPROPRIATENESS
 OF THE
 METHOD USED, AND THE REQUIRED MEANS OF INSPECTING,
 TESTING, AND
 MAINTAINING THE SYSTEM.
 9.3.3 ACCEPTANCE TESTING SHALL BE PERFORMED BY A
 SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
 9.3.4 SMOKE CONTROL SYSTEM OPERATION.
 9.3.4.1 FLOOR- OR ZONE-DEPENDENT SMOKE CONTROL SYSTEMS
 SHALL BE
 AUTOMATICALLY ACTIVATED BY SPRINKLER WATERFLOW OR SMOKE
 DETECTION
 SYSTEMS.
 9.3.4.2 MEANS FOR MANUAL OPERATION OF SMOKE CONTROL
 SYSTEMS
 SHALL BE PROVIDED AT AN APPROVED LOCATION.
  
 3. ADDITIONAL, COMMNETS MAY BE PROVIDED WITH THE
 RE-SUBMITTAL OF THE ABOVE REQUIREMENTS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  