Plan Review Notes For Permit 16020100 |
Permit Number |
16020100 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-08 18:39:17 | FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | PASS WITH A PROVISO ! | | | | C405.2.4 EXTERIOR LIGHTING CONTROLS | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS | | |
|