Date |
Text |
2016-02-10 11:47:30 | CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-6718 |
| [email protected] |
| |
| PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS. |
| PROVIDE ELEVATION OF LANDING AT NEW DOOR. IF LANDING IS |
| GREATER THAN 30" ABOVE GRADE, PROVIDE GUARD. |
| CLARIFY WALL LEGEND, PG A-1. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. |
| |
| FBCR312.1.1 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED |
| WALKING SURFACES, INCLUDING STAIRS, RAMPS AND LANDINGS, |
| THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED |
| VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT |
| WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF |
| THE OPEN SIDE. INSECT SCREENING SHALL NOT BE CONSIDERED |
| AS A GUARD. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| |