Plan Review Notes For Permit 16020057 |
Permit Number |
16020057 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-10 08:35:31 | 1) SHT. S-0 - SCOPE OF WORK REFERS TO THE RELOCATION OF | | A WATER FOUNTAIN BUT THERE IS NO WATER FOUNTAIN SHOWN | | ON THE PLANS. CLARIFY. | | 2) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL | | CHANGES TO THE SANITERY AND WATER PIPNG SYSTEM. 2014 | | FBC SEC. 107.2.1. | | 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN S-2 | | TO A "B: OCCUPANCY.IF IT IS, THEN CCOMPLIANCE WITH THE | | 2014 FBC-EXISTING BUILDING CODE CHAPTER 10 IS REQUIRED. | | SEE SECTIONS 1002 THROUGH 1012. | | 4) PLEASE PLACE THE CORRECT OCCUPANT LOAD ON THE PLANS. | | THE PLANS REFER TO AN OCCUPANT LOAD OF 9, 11 &14. THE | | CORRECT OCCUPANT LOAD FOR A SPACEE OF 915 SQUARE FEET | | IS10 PERSONS PER 2014 FBC TABLE 1004.1.2. | | 5) IF A DRINKING FOUNTAIN IS INSTALLED A MINIMUM OF 2 | | ARE REQUIRED PER THE 2014 FBC- ACCESS. SEC. 211.2. | | 6) CLARIFY HOW YOU ARRIVED AT THE MINIMUM SANITARY | | FIXTURE REQUIREMENTS. THE PLANS SHOW THE REQUIRED WATER | | CLOSETS AS 2, REQUIRED LAVATORIES AS 2, ONE JANITOR | | SINK AND TWO DRINKING FFOUNTAINS.THE PLANS DO NOT SHOW | | THIS NUMBER AND TYPE OF SANITARY FACILITIES. CLARRIFY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|