Plan Review Notes
Plan Review Notes For Permit 16020057
Permit Number 16020057
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-10 08:35:311) SHT. S-0 - SCOPE OF WORK REFERS TO THE RELOCATION OF
 A WATER FOUNTAIN BUT THERE IS NO WATER FOUNTAIN SHOWN
 ON THE PLANS. CLARIFY.
 2) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL
 CHANGES TO THE SANITERY AND WATER PIPNG SYSTEM. 2014
 FBC SEC. 107.2.1.
 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN S-2
 TO A "B: OCCUPANCY.IF IT IS, THEN CCOMPLIANCE WITH THE
 2014 FBC-EXISTING BUILDING CODE CHAPTER 10 IS REQUIRED.
 SEE SECTIONS 1002 THROUGH 1012.
 4) PLEASE PLACE THE CORRECT OCCUPANT LOAD ON THE PLANS.
 THE PLANS REFER TO AN OCCUPANT LOAD OF 9, 11 &14. THE
 CORRECT OCCUPANT LOAD FOR A SPACEE OF 915 SQUARE FEET
 IS10 PERSONS PER 2014 FBC TABLE 1004.1.2.
 5) IF A DRINKING FOUNTAIN IS INSTALLED A MINIMUM OF 2
 ARE REQUIRED PER THE 2014 FBC- ACCESS. SEC. 211.2.
 6) CLARIFY HOW YOU ARRIVED AT THE MINIMUM SANITARY
 FIXTURE REQUIREMENTS. THE PLANS SHOW THE REQUIRED WATER
 CLOSETS AS 2, REQUIRED LAVATORIES AS 2, ONE JANITOR
 SINK AND TWO DRINKING FFOUNTAINS.THE PLANS DO NOT SHOW
 THIS NUMBER AND TYPE OF SANITARY FACILITIES. CLARRIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved