Plan Review Notes
Plan Review Notes For Permit 16020057
Permit Number 16020057
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-10 10:45:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA. A NOTE
 WILL SUFFICE. FBC 107
 2. AN ELECTRICAL PERMIT WILL BE REQUIRED FOR THIS
 PROJECT. ALTHOUGH THE SCOPE OF WORK SAYS NO ELECTRICAL,
 THE CHANGE IN OCCUPANCY TO A CHIROPRACTIC OFFICE
 REQUIRES THE ELECTRICAL INSTALLATION TO BE IN
 CONFORMANCE WITH THE NFPA 70 NEC 2011 ARTICLE 517. ALSO
 THERE IS A NEW EXIT/EM LIGHTING SHOWN.
 3. THE EXAMINATION AREAS WHERE HUMAN BEINGS WILL COME
 IN CONTACT WITH EXAMINATION EQUIPMENT MUST BE WIRED IN
 A MANNER AS DESCRIBE IN NEC 2011 517.13. PLEASE REFLECT
 ON DRAWINGS A NOTE TO INDICATE THIS REQUIREMENT.
 4. GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLET
 SERVING ANY HYDRO MESSAGE EQUIPMENT AS SHOWN ON
 DRAWING. NEC 680- PART VI. CLARIFY WHAT TYPE OF
 EQUIPMENT IS BEING USED.
 5. IF A DRINKING FOUNTAIN IS PART OF THE SCOPE SHOW THE
 RECEPTACLE PROTECTED BY GFCI BREAKER. NEC 422.52
 6. CLARIFY IF THERE IS X-RAY EQUIPMENT BEING INSTALLED.
 FURTHER COMMENTS TO FOLLOW PER CLARIFICATION.
 7. SHOW WINDOW RECEPTACLE OUTLETS NOT SHOWN ON PLANS.
 PLEASE CLARIFY AND COMPLY WITH NEC 220.14G AND NEC
 210.62.
 8. CLARIFY IF ANY CHANGES OR MODIFICATIONS ARE WITHIN
 THE SCOPE OF WORK FOR THE MECHANICAL UNIT. IF NOT SHOW
 AS EXISTING ON DRAWING AND THE LOCATION.
 9. ALL NEW LOADS TO BE REFLECTED ON A PANEL SCHEDULE.
 SHOW THE EXISTING RISER DIAGRAM TO VERIFY CAPACITY
 REQUIREMENTS. FBC 107 NEC 220
 10. CLARIFY IF THERE IS AN EXISTING OUTLET FOR THE
 FRONT SIGN. NEC 600.5
 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  