2016-02-10 10:45:51 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW |
| VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA. A NOTE |
| WILL SUFFICE. FBC 107 |
| 2. AN ELECTRICAL PERMIT WILL BE REQUIRED FOR THIS |
| PROJECT. ALTHOUGH THE SCOPE OF WORK SAYS NO ELECTRICAL, |
| THE CHANGE IN OCCUPANCY TO A CHIROPRACTIC OFFICE |
| REQUIRES THE ELECTRICAL INSTALLATION TO BE IN |
| CONFORMANCE WITH THE NFPA 70 NEC 2011 ARTICLE 517. ALSO |
| THERE IS A NEW EXIT/EM LIGHTING SHOWN. |
| 3. THE EXAMINATION AREAS WHERE HUMAN BEINGS WILL COME |
| IN CONTACT WITH EXAMINATION EQUIPMENT MUST BE WIRED IN |
| A MANNER AS DESCRIBE IN NEC 2011 517.13. PLEASE REFLECT |
| ON DRAWINGS A NOTE TO INDICATE THIS REQUIREMENT. |
| 4. GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLET |
| SERVING ANY HYDRO MESSAGE EQUIPMENT AS SHOWN ON |
| DRAWING. NEC 680- PART VI. CLARIFY WHAT TYPE OF |
| EQUIPMENT IS BEING USED. |
| 5. IF A DRINKING FOUNTAIN IS PART OF THE SCOPE SHOW THE |
| RECEPTACLE PROTECTED BY GFCI BREAKER. NEC 422.52 |
| 6. CLARIFY IF THERE IS X-RAY EQUIPMENT BEING INSTALLED. |
| FURTHER COMMENTS TO FOLLOW PER CLARIFICATION. |
| 7. SHOW WINDOW RECEPTACLE OUTLETS NOT SHOWN ON PLANS. |
| PLEASE CLARIFY AND COMPLY WITH NEC 220.14G AND NEC |
| 210.62. |
| 8. CLARIFY IF ANY CHANGES OR MODIFICATIONS ARE WITHIN |
| THE SCOPE OF WORK FOR THE MECHANICAL UNIT. IF NOT SHOW |
| AS EXISTING ON DRAWING AND THE LOCATION. |
| 9. ALL NEW LOADS TO BE REFLECTED ON A PANEL SCHEDULE. |
| SHOW THE EXISTING RISER DIAGRAM TO VERIFY CAPACITY |
| REQUIREMENTS. FBC 107 NEC 220 |
| 10. CLARIFY IF THERE IS AN EXISTING OUTLET FOR THE |
| FRONT SIGN. NEC 600.5 |
| 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. |
| |
| |
| |
| VALENTINO PEREZ |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6717 |
| [email protected] |
| |