2016-02-08 17:10:06 | ****CORRECTIONS**** |
| |
| ART LANGE - BUILDING INSPECTOR |
| 561-805-6667 [email protected] |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION |
| |
| 1. PERMIT VALUE TOO LOW. PROVIDE A SIGNED CONTRACT AND |
| REVISE PERMIT VALUE WHEN YOU RESUBMIT PLANS. |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2. PROVIDE MEASUREMENTS ON PLANS FOR DOOR ?A?. SHOW |
| COMPLIANCE WITH THE FOLLOWING. FLORIDA ACCESSIBILITY |
| CODE 404.2.4.1 (A) FRONT APPROACH , PULL SIDE AND (C) |
| FRONT APPROACH, PUSH SIDE IF DOOR HAS A CLOSER. SEE |
| FIGURES 404.2.4.1. |
| SHOW DOOR HANDLE HARDWARE AND CLOSER IF USED. |
| |
| 3. SHOW IF DOORS WILL BE PROVIDED FOR THE FOLLOWING |
| ROOMS: OFFICE, MASSAGE ROOM #1 AND EXAM ROOM #1. |
| |
| 4. PLEASE PROVIDE A DETAIL FOR THE RECEPTION PAST |
| THROUGH. SHOW HOW IT WILL COMPLY WITH FLORIDA |
| ACCESSIBILITY CODE SECTION 308. |
| |
| |
| |