2016-02-22 14:47:06REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 - SUBMIT ELECTRICAL DIAGRAM & SPECIFICATIONS SHOWING A
 DEDICATED 20 AMP CIRCUIT WITH A DISCONNECTING MEANS AT
 THE SIGN LOCATION NEC 600.5 , 600.6
  
 - PROVIDE A ASTRONAMICAL TIME CLOCK OR COMBINATION
 PHOTOCELL WITH TIMER FOR EXTERIOR LIGHTING CONTROLS
 FBC-E SECTION C 405.2.4