Plan Review Notes For Permit 16020054 |
Permit Number |
16020054 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-08 18:21:42 | FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | -NEC 600.6 - PROVIDE DISCONNECT SWITCH AT SIGN LOCATION | | -C405.2.4 EXTERIOR LIGHTING CONTROLS | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS | | -FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING | | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | RECORDS MANAGEMENT. |
|