Plan Review Notes
Plan Review Notes For Permit 16020052
Permit Number 16020052
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-08 18:25:05FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 -NEC 600.6 - PROVIDE DISCONNECT SWITCH AT SIGN LOCATION
 -C405.2.4 EXTERIOR LIGHTING CONTROLS
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS
 -FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.