Plan Review Notes For Permit 16020038 |
Permit Number |
16020038 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-09 14:06:54 | BUILDING PROVISO: SHEET A4.0 DETAIL # 4 COVED/ SOFFET | | DETAIL, THE DROPPED CEILING SUB-BASE 3/4 INCH PLYWOOD | | IS REQUIRED TO BE FIRE RESISTANCE-RATED OR | | NONCOMBUSTILE. | | 2014 FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS | | AND CEILINGS ARE REQUIRED TO BE OF | | FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION | | AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES | | GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A | | FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR | | 803.1.2, SHALL BE USED. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|