Plan Review Notes
Plan Review Notes For Permit 16020038
Permit Number 16020038
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-09 14:06:54BUILDING PROVISO: SHEET A4.0 DETAIL # 4 COVED/ SOFFET
 DETAIL, THE DROPPED CEILING SUB-BASE 3/4 INCH PLYWOOD
 IS REQUIRED TO BE FIRE RESISTANCE-RATED OR
 NONCOMBUSTILE.
 2014 FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS
 AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A
 FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR
 803.1.2, SHALL BE USED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  