Plan Review Notes For Permit 16020030 |
Permit Number |
16020030 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-04-04 05:53:31 | NONE OF THE PLUMBING COMMENTS FROM THE FIRST REVIEW | | HAVE BEEN ADDRESSED. | | | | 1) PROVIDE MANUFACTURER'S SPECIFICATIONS ON THE PUMP, | | TSUNAMI VALVE,& MDX REMOVAL SYSTEM. FBC | | SEC.107.2.1.SUBMIT COMPLETE SPECIFICATIONS FOR THE | | PUMP. THE ONE SHEET THAT WAS SUBMITTED IS UNACCEPTABLE. | | 2) SUPPLY TOTAL DYNAMIC HEAD CALCULATIONS, PUMP | | CURVE,TURNOVER RATE, ETC. FBC SEC.107.2.1. | | 3) PLEASE REVISE THE CODE REFERENCE ON THE THE PLANS TO | | FBC-RESIDENTIAL. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|