2016-04-04 05:53:31NONE OF THE PLUMBING COMMENTS FROM THE FIRST REVIEW
 HAVE BEEN ADDRESSED.
  
 1) PROVIDE MANUFACTURER'S SPECIFICATIONS ON THE PUMP,
 TSUNAMI VALVE,& MDX REMOVAL SYSTEM. FBC
 SEC.107.2.1.SUBMIT COMPLETE SPECIFICATIONS FOR THE
 PUMP. THE ONE SHEET THAT WAS SUBMITTED IS UNACCEPTABLE.
 2) SUPPLY TOTAL DYNAMIC HEAD CALCULATIONS, PUMP
 CURVE,TURNOVER RATE, ETC. FBC SEC.107.2.1.
 3) PLEASE REVISE THE CODE REFERENCE ON THE THE PLANS TO
 FBC-RESIDENTIAL.
  
 PLUMBING PLAN REVIEW