2016-02-05 10:42:131ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. YOU SHALL PROVIDE AN ELECTRICAL RISER DIAGRAM
 INDICATING ALL THE PROPOSED POOL EQUIPMENT AND
 LIGHTING. THIS SHOULD ALSO INDICATE THE TYPE OF POOL
 LIGHTING PROPOSED IF ANY.
 2. FROM THE SITE PLAN PROVIDED, ACTUAL MEASUREMENTS FOR
 THE LOCATION OF OVERHEAD SERVICE CONDUCTORS IN RELATION
 TO THE POOL WOULD NOT BE PRACTICAL. THE PLAN HAS A NOTE
 INDICATING THAT THE SERVICE DROP WILL BE REMOVED BY THE
 OWNER. VERIFY OVERHEAD CONDUCTOR CLEARANCES AS
 INDICATED IN NEC 680.8 IF IT IS TO REMAIN AND REVISE
 THE DRAWING TO REMOVE SUCH NOTE.
 3. WHEN DIGGING THE HOLE FOR THE POOL SHELL, ASCERTAIN
 COMPLIANCE WITH NEC 680.10 WHICH PROHIBITS ANY
 UNDERGROUND WIRING WITHIN 5? HORIZONTALLY OF THE POOL
 SHELL UNLESS THE WIRING IS DIRECTLY RELATED TO THE
 POOL.
 4. ALL POOL BONDING AS REQUIRED BY NEC 680.26 SHALL BE
 INDICATED ON DRAWINGS.
 5. IN ADDITION TO THE ABOVE, COMPLIANCE WITH FBC-R
 CHAPTER 42.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  