2016-02-05 10:42:13 | 1ST ELECTRICAL REVIEW NOTES: |
| REVIEWED FOR COMPLIANCE WITH: |
| FBC 5TH EDITION 2014 |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| 1. YOU SHALL PROVIDE AN ELECTRICAL RISER DIAGRAM |
| INDICATING ALL THE PROPOSED POOL EQUIPMENT AND |
| LIGHTING. THIS SHOULD ALSO INDICATE THE TYPE OF POOL |
| LIGHTING PROPOSED IF ANY. |
| 2. FROM THE SITE PLAN PROVIDED, ACTUAL MEASUREMENTS FOR |
| THE LOCATION OF OVERHEAD SERVICE CONDUCTORS IN RELATION |
| TO THE POOL WOULD NOT BE PRACTICAL. THE PLAN HAS A NOTE |
| INDICATING THAT THE SERVICE DROP WILL BE REMOVED BY THE |
| OWNER. VERIFY OVERHEAD CONDUCTOR CLEARANCES AS |
| INDICATED IN NEC 680.8 IF IT IS TO REMAIN AND REVISE |
| THE DRAWING TO REMOVE SUCH NOTE. |
| 3. WHEN DIGGING THE HOLE FOR THE POOL SHELL, ASCERTAIN |
| COMPLIANCE WITH NEC 680.10 WHICH PROHIBITS ANY |
| UNDERGROUND WIRING WITHIN 5? HORIZONTALLY OF THE POOL |
| SHELL UNLESS THE WIRING IS DIRECTLY RELATED TO THE |
| POOL. |
| 4. ALL POOL BONDING AS REQUIRED BY NEC 680.26 SHALL BE |
| INDICATED ON DRAWINGS. |
| 5. IN ADDITION TO THE ABOVE, COMPLIANCE WITH FBC-R |
| CHAPTER 42. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |