2016-01-29 14:50:32 | 16010961 | | 701 NORTHPOINT PARKWAY # 402 | | COMMERCIAL REVISION TO PERMIT # 15100864 | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE AN ACCURATE PANEL SCHEDULE FOR PANEL ?H4? THAT | | SHOWS ALL LOADS INCLUDING THE TRANSFORMER. PANEL ?A? IS | | NOT SHOWN ON THE RISER PLAN. NEC 210.15 | | PROVIDE GFCI PROTECTION FOR COUNTER TOP RECEPTACLES | | NEAR THE SINK. NEC 210.8 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | | | |
|