Plan Review Notes For Permit 16010945 |
Permit Number |
16010945 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-08 14:36:43 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010945 | | 2/8/16 | | | | 1) PROVIDE THE SCOP RATING FOR THE NEW IT ROOM AC | | SYSTEM- SEE TABLE C403.2.3(10) FBC-14 ENERGY | | CONSERVATION. | | 2) THE CONDENSATE FROM THE NEW FC-1 SHALL NOT DRAIN | | INTO THE CITY SANITARY SEWER IN COMPLIANCE WITH | | SEC.90-126 WPBB CODE OR ORDINANCES. | | 3) PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION | | DETAIL FOR SD-1. | | 4) IT APPEARS THAT A FD OR SD IS MISSING AT THE 6X4 | | DOUBLE DEFLECTION SUPPLY GRILL AT THE MEDICAL RECORDS | | FIRE-RATED WALL. | | 5) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR MOUNTING | | CU-1 ON THE ROOF. | | 6) SHEET M2.0: PLEASE LABEL ALL THE DUCTS, DIFFUSERS, | | GRILLS, AIR HANDLERS AND CONDENSERS AS EITHER NEW, | | EXISTING, OR RELOCATED ON THE PLANS TO CLARIFY THE | | SCOPE OF WORK FOR THE PROJECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|