2016-02-08 14:36:431ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010945
 2/8/16
  
 1) PROVIDE THE SCOP RATING FOR THE NEW IT ROOM AC
 SYSTEM- SEE TABLE C403.2.3(10) FBC-14 ENERGY
 CONSERVATION.
 2) THE CONDENSATE FROM THE NEW FC-1 SHALL NOT DRAIN
 INTO THE CITY SANITARY SEWER IN COMPLIANCE WITH
 SEC.90-126 WPBB CODE OR ORDINANCES.
 3) PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION
 DETAIL FOR SD-1.
 4) IT APPEARS THAT A FD OR SD IS MISSING AT THE 6X4
 DOUBLE DEFLECTION SUPPLY GRILL AT THE MEDICAL RECORDS
 FIRE-RATED WALL.
 5) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR MOUNTING
 CU-1 ON THE ROOF.
 6) SHEET M2.0: PLEASE LABEL ALL THE DUCTS, DIFFUSERS,
 GRILLS, AIR HANDLERS AND CONDENSERS AS EITHER NEW,
 EXISTING, OR RELOCATED ON THE PLANS TO CLARIFY THE
 SCOPE OF WORK FOR THE PROJECT.
  