2016-02-16 06:55:50INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND
 DATA, ACCESS CONTROLS, SECURITY ETC. A NOTE WILL
 SUFFICE.
 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL
 SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING
 SHOWN FOR THIS PROJECT. PER NEC 230.2 SPECIAL
 PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING.
 COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE
 SHOWN.
 3. SHOW ACTUAL AIC CALCULATIONS FOR THE NEW SERVICE
 SHOWN. FBC 107
 4. PROVIDE PER FBC EC 405.7 FEEDER AND BRANCH CIRCUIT
 VOLTAGE DROP CALCULATIONS
 5. GENERAL NOTES TO INDICATE REQUIREMENTS OF FBC EC
 405.4 COMPLETION DOCUMENTS SEE VERBIAGE IN THE CODE. A
 NOTE WILL SUFFICE.
 6. SHOW A RISER DIAGRAM REFLECTING THE ONE-LINE FOR THE
 NEW ELECTRICAL SERVICE.
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  