2016-02-08 11:36:18 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16010945 |
| ADD: 2000 CONTINENTAL DR. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ??????? |
| E-MAIL: ?????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. FEB. 08/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET A2.0 AND A6.1. BOTH PAGES SHOW DETAILS OF A |
| NEW MEZZANINE: |
| 1A) SHEET A2.0 SHOWS AN ALATERNATIVE TO EXPAND THE |
| MEZZANINE. PLEASE SEE 2014 FLORIDA BUILDING CODE W 2014 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION OF |
| CONSTRUCTION DRAWINGS. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES. |
| IF THE DESIGNER WISHES TO EXPAND THE MEZZANINE AFTER |
| THE PERMIT ISSUANCE IT MAY COME IN AS A REVISION. |
| |
| 1B) PLEASE PROVIDE THE SQUARE FEET OF AREA IN ROOMS113 |
| & 114 THAT WILL COMMUNICATE WITH THE MEZZANINE TO SEE |
| IF THERE IS CODE COMPLIANCE WITH: |
| 2014 505.2.1 AREA LIMITATION. THE AGGREGATE AREA OF A |
| MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT |
| GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM |
| OR SPACE IN WHICH THEY ARE LOCATED. THE ENCLOSED |
| PORTION OF A ROOM SHALL NOT BE INCLUDED IN A |
| DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH |
| THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWABLE |
| MEZZANINE AREA, THE AREA OF THE MEZZANINE SHALL NOT BE |
| INCLUDED IN THE FLOOR AREA OF THE ROOM. THE ALTERNATE |
| DESIGN FOUND ON SHEET A2.0, A2.1, A2.2, A2.3 & A2.5 OF |
| 358 SQ. FT. APPEARS THE SQUARE FOOTAGE IS OVER THE |
| ALLOWABLE 33% OF THE FLOOR AREA. |
| |
| 1C) SHEET A2.0 & LS2.0 BOTH SHOW THE CORRIDOR 110 WITH |
| A 1 HOUR FIRE RATING. THE PLANS ONLY STATE FOR THE |
| CEILING 1 LAYER OF TYPE X 5/8 GYPSUMFOR BOTH SIDES OF |
| THE CEILING. THE PLANS DO NOT PROVIDE A GYPSUM |
| ASSOCIATION OR UL LISTING FOR THE CEILING ASSEMBLY NOR |
| THE WALL ASSEMBLY. FBC-B 1018.1. |
| |
| 1D) SHEET A2.0 SHOWS THE COORIDOR ON THE RIGHT SIDE |
| THERE IS 2 DOORS 111 & 112 BOTH SHOW AS A 45 MINUE |
| RATED DOOR, BUT TO THE RIGHT SIDE OF THE CORRIDOR THERE |
| IS NO DOOR SEPARATING THE CORRIDOR FROM THE TREATMENT |
| ROOMS. FBC-B 1018.6 CORRIDOR CONTINUITY. |
| |
| 2) SHEET A6.1: |
| 2A) SHEET A6.1 SHOWS A CUT ELEVATION THROUGH THE |
| MEZZANINE LEVEL. THE PLANS INDICATE THE SCALE AS 3/4 |
| INCH EQUALS A FOOT, I BELIEVE THIS IS A TYPO AND SHOULD |
| BE 3/8 INCH EQUALS A FOOT. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 2B) THE DESIGNER OF RECORD HAS NOTED THAT THE MEZANINE |
| IS A DESIGN BUILD. A MANUFACTURED MEZANINE SYSTEM, |
| SHALL INCLUDE COLUMNS, BEAMS AND BAR GRATINGFLOOR, |
| RAILINGS, SHIPS LADDER FROM THE MEZANINE MANUFACTURER. |
| WITH THE FOOTING DESIGN PER THE MANUFACTURERS |
| RECOMMENDATIONS OR MANUFACTURERS STRUCTURAL CONSULTANT. |
| THE DESIGNER OF RECORD HAS NOT PROVIDED THE MEZZANINE |
| MANUFACTURER THE REQUIRED DESIGN CRITERIA FOR THE |
| MEZZANINE MANUFACTURER TO DESIGN TOO. 2014 FBC-B TABLE |
| 1607.1 (31) 125PSF OR 250 PSF (FOOTNOTE M) MINIMUM |
| UNIFORMLY DISTRIBUTED LIVE LOADS. |
| |
| 2C) 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR |
| WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR |
| INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED |
| 50 PSF (2.40 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE |
| CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH |
| STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT |
| SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES |
| 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL |
| NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY |
| SECTION 106.1, HAVE BEEN INSTALLED. |
| |
| 2D) PLEASE NOTE ONLY LICENSED FLORIDA P.E. CAN PRCATICE |
| ENGINEEERING IN THE STATE OF FLORIDA. FLORIDA STATUTE |
| 471.015. THE STEEL MEZZANINE STAIRS, HANDRAIL, |
| GUARDRAIL SYSTEM AS WELL AS FOUNDATION WILL ALL NEED TO |
| BE ENGINEERED. |
| |
| 2E) BEFORE THE MEZZANINE DRAWING ARE TO BE SUBMITTED |
| TOTHIS OFFICE THEY MUST BE REVIEWED BY THE ARCHITECT OF |
| RECORD AND SHOP DRAWING STAMP OF APPROVAL AFFIXED. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |