Plan Review Notes
Plan Review Notes For Permit 16010944
Permit Number 16010944
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-25 11:16:05THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW LOCATION OF THE MAIN ELECTRICAL DISCONNECT AND
 ELECTRICAL PANELS. VERIFY ALL REQUIRED SAFETY
 CLEARANCES. VERIFY ALL REQUIRED SERVICE GROUNDING.
 PROVIDE AN ELECTRICAL PANEL SCHEDULE SHOWING ALL NEW
 AND EXISTING CIRCUITS. PROVIDE A SUMMARY LOAD
 CALCULATION. ON THE PLANS SHOW THE LOCATION OF ALL NEW
 AND EXISTING ELECTRICAL SWITCHES AND OUTLETS. NEC
 110.26; 215.5; 408.4, FBC R E3405.3, 3706.2
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOM.
 NEC 210.11 (C) (3); FBC R E3703.4
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
 FBC R 3703.3
  
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014
 FBC R 314, 315
  
 SHOW GFCI PROTECTED RECEPTACLES WHERE REQUIRED. NEC
 210.8; FBC R 3902
  
 VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12;
 FBC R 3902.12
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R4002.14
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  