Plan Review Notes For Permit 16010944 |
Permit Number |
16010944 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-25 11:16:05 | THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR. | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | SHOW LOCATION OF THE MAIN ELECTRICAL DISCONNECT AND | | ELECTRICAL PANELS. VERIFY ALL REQUIRED SAFETY | | CLEARANCES. VERIFY ALL REQUIRED SERVICE GROUNDING. | | PROVIDE AN ELECTRICAL PANEL SCHEDULE SHOWING ALL NEW | | AND EXISTING CIRCUITS. PROVIDE A SUMMARY LOAD | | CALCULATION. ON THE PLANS SHOW THE LOCATION OF ALL NEW | | AND EXISTING ELECTRICAL SWITCHES AND OUTLETS. NEC | | 110.26; 215.5; 408.4, FBC R E3405.3, 3706.2 | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOM. | | NEC 210.11 (C) (3); FBC R E3703.4 | | | | PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2); | | FBC R 3703.3 | | | | SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014 | | FBC R 314, 315 | | | | SHOW GFCI PROTECTED RECEPTACLES WHERE REQUIRED. NEC | | 210.8; FBC R 3902 | | | | VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12; | | FBC R 3902.12 | | | | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC | | 406.2; FBC R4002.14 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-373-3701 | | | | |
|