Plan Review Notes For Permit 16010936
Permit Number 16010936
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-28 19:01:592010 FBC
 REVISION DENIED
  
 1) THE ORIGINAL APPROVED PLANS WERE PRODUCED BY ANOTHER
 A/C CONTRACTOR. THE NEW PLANS FROM A DIFFERENT A/C
 CONTRACTOR CAN NOT REFER TO DETAILS ON THE OTHER
 CONTRACTOR'S DRAWINGS. THE NEW CONTRACTOR IS REQUIRED
 TO REPRODUCE THE PLANS ENTIRELY WITH ALL DETAILS AND
 SCHEDULES. FBC 107.2.3 AND FS 471.003 (2)(H)
  
 2) SHOW COMPLIANCE WITH 2010 FBCR - M1503.4 FOR
 REQUIRED MAKEUP AIR FOR THE 600 CFM KITCHEN EXHAUST
 HOOD.
  
 3) THE NEW MECHANICAL PLANS ARE MISSING SOME OF THE
 WALLS FROM THE FLOOR PLANS. FBC 107.2.1
  