Plan Review Notes For Permit 16010936 |
Permit Number |
16010936 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-28 19:01:59 | 2010 FBC | | REVISION DENIED | | | | 1) THE ORIGINAL APPROVED PLANS WERE PRODUCED BY ANOTHER | | A/C CONTRACTOR. THE NEW PLANS FROM A DIFFERENT A/C | | CONTRACTOR CAN NOT REFER TO DETAILS ON THE OTHER | | CONTRACTOR'S DRAWINGS. THE NEW CONTRACTOR IS REQUIRED | | TO REPRODUCE THE PLANS ENTIRELY WITH ALL DETAILS AND | | SCHEDULES. FBC 107.2.3 AND FS 471.003 (2)(H) | | | | 2) SHOW COMPLIANCE WITH 2010 FBCR - M1503.4 FOR | | REQUIRED MAKEUP AIR FOR THE 600 CFM KITCHEN EXHAUST | | HOOD. | | | | 3) THE NEW MECHANICAL PLANS ARE MISSING SOME OF THE | | WALLS FROM THE FLOOR PLANS. FBC 107.2.1 | | |
|