2016-01-28 18:10:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE E(4) SYSTEM SELECTED ON PAGE 24 OF NOA NO.
 14-0529.02 HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF,
 WHICH IS NOT ADEQUATE FOR THE PERIMETER AND CORNER ROOF
 AREAS OF THE FLAT ROOF OF A STRUCTURE WITH A 15' MRH IN
 EXPOSURE C. SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS AS REQUIRED BY LIMITATION #7 ON PAGE
 42 OF THE NOA.
  
  