Plan Review Notes For Permit 16010922 |
Permit Number |
16010922 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-28 18:10:42 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE E(4) SYSTEM SELECTED ON PAGE 24 OF NOA NO. | | 14-0529.02 HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF, | | WHICH IS NOT ADEQUATE FOR THE PERIMETER AND CORNER ROOF | | AREAS OF THE FLAT ROOF OF A STRUCTURE WITH A 15' MRH IN | | EXPOSURE C. SUBMIT TWO SETS OF SIGNED AND SEALED RAS | | 117 CALCULATIONS AS REQUIRED BY LIMITATION #7 ON PAGE | | 42 OF THE NOA. | | | | |
|