2016-02-08 12:12:55 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010904 | | 2/8/16 | | | | 1) SHEET M000: THE DRAWINGS AND PRINT IN DETAIL N0.3 IS | | VERY FAINT AND NOT SUITABLE FOR PLAN REVIEW OR COMPUTER | | FILE SCANNING- PLEASE SUBMIT LEGIBLE PLANS PER SECTION | | 107.2 WPB AMENDMENTS TO THE FBC-14 BUILDING CODE. | | 2) M100: THE PRINT ION THE SYMBOL LEGEND IS VERY FAINT | | AND NOT LEGIBLE- PLEASE SUBMIT LEGIBLE PLANS. | | 3) REFER TO SECTION 809.2 FBC-14 EXISITNG BUILDING AND | | PROVIDE A VENTILATION CALCULATIONS FOR THE PROPOSED NEW | | OFFICES- SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A | | AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|