Plan Review Notes For Permit 16010904 |
Permit Number |
16010904 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-12 13:18:33 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | ALARM, AUDIO/SPEAKERS, PHONE AND DATA. A NOTE WILL | | SUFFICE. | | 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT | | INFORMATION: FOR EXAMPLE, NEW LOADS, AIC RATING ETC. | | FBC 107. | | 3. ID THE FLOOR PLAN WITH CIRCUIT DESIGNATION. FBC | | 107.3 | | 4. PLEASE SHOW AUTOMATIC LIGHTING CONTROLS COMPLIANCE | | PER FBC EC 405 | | 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|