Plan Review Notes
Plan Review Notes For Permit 16010889
Permit Number 16010889
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-10 13:58:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC R308.4.5 REQUIRES SAFETY GLAZING IN THE
 BATHROOM. GLAZING IN WALLS, ENCLOSURES OR FENCES
 CONTAINING OR FACING HOT TUBS, SPAS, WHIRLPOOLS,
 SAUNAS, STEAM ROOMS, BATHTUBS, SHOWERS AND INDOOR OR
 OUTDOOR SWIMMING POOLS WHERE THE BOTTOM EXPOSED EDGE OF
 THE GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED
 VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE SHALL
 BE CONSIDERED A HAZARDOUS LOCATION. THIS SHALL APPLY TO
 SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING.
  