2016-02-11 13:53:18INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE AND SHOW ON DRAWING THE RECEPTACLE
 OUTLETS NOW REQUIRED FOR WALL SPACE DUE TO ENCLOSING
 AREA. COMPLY WITH FBC RES- SEC E39012.1 AND 2.2
 2. SHOW AND PROVIDE THE REQUIRED LIGHTING OUTLETS PER
 FBC RES- SEC E3903.2 AND .3. INTERIOR AND EGRESS
 LOCATIONS
 3. PROVIDE A NOTE TO COMPLY WITH AFCI PROTECTION FOR
 BRANCH CIRCUITS AND TAMPER RESISTANT RECEPTACLE PER FBC
 RES- SEC E3902.12 AND E4002.14
 4. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER
 ALTERATION. PROVIDE OR SHOW EXISTING SMOKE DETECTORS TO
 COMPLY. SEE EXCEPTION 314.4-3 FOR EASE OF COMPLIANCE.
 5. FURTHER COMMENTS MAT FOLLOW UPON RESUBMITTAL.
 6. ELECTRICAL PERMIT REQUIRED
  