2016-02-05 13:39:431ST REVIEW: FBC 2014 MECHANICAL & EXISTING BUILDING
 CODE
 PERMIT #16010805
 2/5/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED NEW TENANT SPACE PER SECTION 809.2 FBC-14
 EXISTING BUILDING CODE AND TABLE 403.3 FBC-14
 MECHANICAL.
 2) THE VAV SCHEDULE INDICATES VAV-12 BUT IT IS NOT
 SHOWN IN THE LAYOUT PLAN. VAV-8 IS SHOWN IN THE LAYOUT
 PLAN BUT NOT IN THE SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER