Plan Review Notes For Permit 16010805 |
Permit Number |
16010805 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-08 14:06:52 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE A FEEDER DETAIL AND SUMMARY LOAD CALCULATION | | FOR THIS OCCUPANCY. NEC 215.5 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | MEANS. NEC 110.16, 110.22 | | | | PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT | | SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH | | ADEQUATE HEAD ROOM. NEC 110.26 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-373-3701 | | |
|