2016-02-05 09:50:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010805
 ADD: 1645 PALM BEACH LAKES SUITE # 1050
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 05/2016
 ACTION: DENIED
  
 1) SHEET A-2 VERSES A-3. INDICATED ON SHEET A-2 IN THE
 WALL LEGEND IS THE WALL TYPE FOR A 1-HOUR FIRE RATED
 PARTITION. SHEET A-2 SHOWS VARIOUS NEW WALLS WITHIN THE
 TENANT SPACE WITH A WALL DETAIL OF 1/A3 WHICH INDICATES
 THIS TYPE OF WALL AS A 1-HOUR FIRE RATED PARTITION. THE
 DESIGNER CAN DESIGN OVER AND ABOVE THE MINIMUM CODE, IF
 THIS THE ENTENT THEN THE DOORS WITHIN THE RATED WALL
 WILL ALSO NEED TO COMPLY WITH OPENING PROTECTIVES FOUND
 UNDER 2014 FBC-B TABLE716.5.
  
 2) THE COMBINED AREA OF SUITE 1050 IS NOW 6098 OR
 6098/100= 61 OCCUPANTS. THE FRONT ENTRY DOORS SWING,
 SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS OR A GROUP H OCCUPANCY.2014 FBC-B
 1008.1.2. NEW WORK SHALL NOT CREATE A NONCONFORMITY.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3) SHEET A-3 THE BREAKROOM # 114 SHOWS A MICROWAVE ON A
 SHELF APPROXIMATELY 5 FEET ABOVE FINISH FLOOR. PLEASE
 REVIEW THE 2014 FBC-ACCESSIBILITY CODE FOR OPERABLE
 PARTS:
 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  