2016-02-23 14:19:11 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL/EXISTING |
| BUILDING |
| |
| FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW |
| SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R |
| M15. |
| |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| R403.6.1 EQUIPMENT SIZING. |
| HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| OTHER APPROVED HEATING AND COOLING CALCULATION |
| METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| EXHAUST SYSTEMS. |
| |
| R403.6.1.1 COOLING EQUIPMENT CAPACITY. |
| COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS |
| TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL |
| LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE |
| TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE |
| SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE |
| SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE |
| CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL |
| NOT BE LESS THAN THE CALCULATED LATENT LOAD. |
| |