Plan Review Notes
Plan Review Notes For Permit 16010798
Permit Number 16010798
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-22 13:22:30PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE NEW
 BATHROOM. NEC 210.11 (C) (3); FBC R E3703.4
  
 THE ELECTRIC PANEL CANNOT BE LOCATED IN A BATHROOM. NEC
 240.24 (E); FBC R E3705.7
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  
  