Plan Review Notes For Permit 16010798 |
Permit Number |
16010798 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-22 13:22:30 | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE NEW | | BATHROOM. NEC 210.11 (C) (3); FBC R E3703.4 | | | | THE ELECTRIC PANEL CANNOT BE LOCATED IN A BATHROOM. NEC | | 240.24 (E); FBC R E3705.7 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-373-3701 | | | | | | |
|