Plan Review Notes For Permit 16010797 |
Permit Number |
16010797 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-29 13:02:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. SHEET A - 2, INDICATES TWO DOORS LABELED AS "C". THE | | DOOR SCHEDULE DOES NOT INDICATE A "C" DOOR DESCRIPTION. | | PLEASE CORRECT. | | | | 2. SHEET 3 - 1, INDICATES CARD READERS ON EXIT DOORS, | | PROVIDE NOTE INDICATING THAT THEY SHALL DELAY OR | | RESTRICT EGRESS. | | | | 3. SHEET 3 - 1, PROVIDE A NOTE INDICATING THAT FIRE | | ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|