2016-02-12 08:02:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE REFERENCE ON ELECTRICAL SPECS TO
 INDICATE NEW SECTIONS OF THE FLORIDA ENERGY
 CONSERVATION CODE 2014 5TH EDITION. SECTIONS HAVE BEEN
 MOVED OVER TO FBC EC 405.7 NOT SECTION 505
 2. PROVIDE A NOTE TO INDICATE THE CARD READERS AND
 DATA/PHONES TO BE ON SEPARATE PERMIT. A NOTE WILL
 SUFFICE. FBC 107.
 3. PROVIDE A NOTE TO MAINTAIN FIRE RATING ON DEMISING
 WALLS. NEC 300.21
  
  
  