2016-02-05 06:45:41 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16010797 |
| ADD: 701 NORTHPOINT PKY. SUITE 150 |
| CONT: CHANDLIER |
| TEL: 791-6934 |
| E-MAIL: JOHN @BUILDERCCC.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. FEB. 05/2016 |
| ACTION: DENIED |
| |
| 1) SHEET A-2: |
| |
| 1A) THE OFFICE 104 (2) OFFICES 104) AND CONFERENCE ROOM |
| # 107 BOTH SHOW A DETAIL 1/ A-3 WHICH IS A 1-HOUR FIRE |
| RATED WALL. IN THE OFFICE DOORWAY A DOOR IDENTIIFED AS |
| A B TYPE DOOR IS SHOWN. ONSHEET A-3 THE B TYPE DOORWAY |
| IS SHOWN AS A SOLID CORE WOOD DOOR WITH A 3/8 INCH |
| TEMPERED GLASS. PLEASE PROVIDE COMPLIANCE WITH SECTION |
| TABLE 716.5 OPENING FIRE PROTECTION ASSEMBLIES, RATINGS |
| AND MARKINGS & TABLE 716.6 FIRE WINDOW ASSEMBLY FIRE |
| PROTECTION RATINGS. |
| |
| 1B) IN THE CONFERENCE ROOM THE DOOR IS IDENTIFIED AS A |
| DOOR TYPE C BUT IS NOT SHOWN ON THE DOOR SCHEDULE FOUND |
| ON SHEET A3. THE FLOOR PLANS DO APPEAR TO BE THE SAME |
| CONFIGURATION AS THE OFFICE DOOR AND SIDELIGHT IN |
| OFFICE 104. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |