2016-01-22 16:04:12 | 1ST REVIEW: FBC 2014 BUILDING |
| PERMIT #16010738 |
| 01/22/16 |
| |
| 1) IN ACCORDANCE WITH SECTION 1609.4 FBC-14 BUILDING, |
| THE HOUSE AND ROOF PROJECT IS LOCATED IN EXPOSURE D. |
| PROVIDE CORRECTED CALCULATIONS AND AND SUBMITTALS |
| INDICATING COMPLIANCE. PLEASE NOTE THAT THE PRODUCT |
| APPROVALS ARE ISSUED WITH ENGINEERING CERTIFICATIONS, |
| AND THE ENGINEER OF RECORD MAY PROVIDE A REVIEW |
| SIGNATURE ON THE DOCUMENTS, BUT NOT RAISED SEALS AND |
| SIGNATURES. |
| 2) PLEASE SEE NOTE 5.5.1 ON PAGE 3 OF THE ENTEGRA ROOF |
| TILE PRODUCT APPROVAL AND INDICATE THE TYPE AND SIZE OF |
| MECHANICAL TILE FASTENERS. THE SUBMITTED WORK SHEET |
| APPEARS TO INDICATE BOTH SCREWS AND NAILS? |
| 3) PLEASE REFER TO SECTION 708.8 FBC-14 EXISTING |
| BUILDING. BECAUSE THE VALUE OF THE HOUSE NEXCEEDS |
| $300,000, ROOF TO WALL CONNECTIONS MAY HAVE TO BE |
| IMPROVED. |
| 708.8 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT |
| SINGLE FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND |
| REPLACED ON A BUILDING THAT IS LOCATED IN THE |
| WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA |
| BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE |
| OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR |
| FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT |
| PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR |
| PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE: |
| (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| REQUIRED BY SECTION 708.8.1. |
| (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN |
| THE COST OF REROOFING. |
| EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| REQUIRED TO COMPLY WITH THIS SECTION. |
| |