Plan Review Notes
Plan Review Notes For Permit 16010659
Permit Number 16010659
Review Stop G
Sequence Number 1
Notes
Date Text
2016-01-28 05:32:591) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. IS THE FIREPLACE GAS/ IF SO,
 SHOW IT ON THE GAS PIPING RISER.REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
 2)INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON
 THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2.
 3) INDICATE THE GAS APPLIANCE ON THE GAS RISER.
 4) A SEPARATE PERMIT IS REQUIRED FOR THE GAS SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  