Plan Review Notes For Permit 16010623 |
Permit Number |
16010623 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-17 09:53:29 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010623 | | 3/17/16 | | | | 1) COMMENTS #3 & 4 FROM THE 1ST REVIEW STILL EXIST. I | | AM REPRINTING THEM BELOW. ADDITIONALLY, PLEASE SUBMIT | | AC CHANGE-OUT FORMS FOR THE REPLACED THROUGH-THE-WALL | | AC SYSTEMS, AND PROVIDE EQUIPMENT SCHEDULES ON THE | | PLANS. | | | | 1ST REVIEW: | | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | PROPOSED TENANT SPACES. SHOW THE REQUIRED AND PROVIDED | | CFM'S OF OUTDOOR AIR. | | 4) ENERGY COMPLIANCE IS REQUIRED IN ACCORDANCE WITH | | SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. SEE THE | | DEFINITION OF RENOVATED BUILDING- SECTION 202. PLEASE | | NOTE THE NEW EXTERIOR DOORS MUST MEET OR EXCEED THE | | CURRENT EFFICIENCY RATINGS ACCORDING TO THE CODE. | | | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|