Plan Review Notes For Permit 16010623 |
Permit Number |
16010623 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-15 11:24:49 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | PENDING COMMENTS NOT ADDRESSED: | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND | | DATA. A NOTE WILL SUFFICE. | | 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL | | SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING | | SHOWN FOR THIS PROJECT. PER NEC 230.2; SPECIAL | | PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING. | | COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE | | SHOWN. | | 5. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT | | INFORMATION: FOR EXAMPLE, AIC RATING ETC. FBC 107. | | 7. PROVIDE SPEC SHEETS FOR INSTANT- HOT WH SELECTED TO | | VERIFY LOADS, FBC 107 | | 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|