Plan Review Notes
Plan Review Notes For Permit 16010623
Permit Number 16010623
Review Stop E
Sequence Number 2
Notes
Date Text
2016-03-15 11:24:492ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND
 DATA. A NOTE WILL SUFFICE.
 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL
 SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING
 SHOWN FOR THIS PROJECT. PER NEC 230.2; SPECIAL
 PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING.
 COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE
 SHOWN.
 5. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT
 INFORMATION: FOR EXAMPLE, AIC RATING ETC. FBC 107.
 7. PROVIDE SPEC SHEETS FOR INSTANT- HOT WH SELECTED TO
 VERIFY LOADS, FBC 107
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  