2016-01-24 05:13:40 | 1)SHT.A100 SHOWS CONTINUOUS GRAB BARS IN THE ACCESSIBLE |
| TOILET ROOMS. GRAB BARS SHALL COMPLY WITH 2014 |
| FBC-ACCESS. SECS.604.5.1, 604.5.2, & 609. NOTE 11 ON |
| A11 INDDICATES 24" & 36" GRAB BARS.CLARIFY. |
| 604.5.1 SIDE WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| FROM THE REAR WALL. |
| 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| 609.1 GENERAL. |
| GRAB BARS IN TOILET FACILITIES AND BATHING FACILITIES |
| SHALL COMPLY WITH 609. |
| 609.2 CROSS SECTION. |
| GRAB BARS SHALL HAVE A CROSS SECTION COMPLYING WITH |
| 609.2.1 OR 609.2.2. |
| 609.2.1 CIRCULAR CROSS SECTION. |
| GRAB BARS WITH CIRCULAR CROSS SECTIONS SHALL HAVE AN |
| OUTSIDE DIAMETER OF 11/4 INCHES (32 MM) MINIMUM AND 2 |
| INCHES (51 MM) MAXIMUM. |
| 609.2.2 NON-CIRCULAR CROSS SECTION. |
| GRAB BARS WITH NON-CIRCULAR CROSS SECTIONS SHALL HAVE A |
| CROSS-SECTION DIMENSION OF 2 INCHES (51 MM) MAXIMUM AND |
| A PERIMETER DIMENSION OF 4 INCHES (100 MM) MINIMUM AND |
| 4.8 INCHES (120 MM) MAXIMUM. |
| 609.3 SPACING. |
| THE SPACE BETWEEN THE WALL AND THE GRAB BAR SHALL BE 1 |
| 1/2 INCHES (38 MM). THE SPACE BETWEEN THE GRAB BAR AND |
| PROJECTING OBJECTS BELOW AND AT THE ENDS SHALL BE 1 1/2 |
| INCHES (38 MM) MINIMUM. THE SPACE BETWEEN THE GRAB BAR |
| AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 |
| MM) MINIMUM. |
| EXCEPTION: THE SPACE BETWEEN THE GRAB BARS AND SHOWER |
| CONTROLS, SHOWER FITTINGS, AND OTHER GRAB BARS ABOVE |
| SHALL BE PERMITTED TO BE 1 1/2 INCHES (38 MM) MINIMUM. |
| 609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE. |
| 2) CLEARLY SHOW ON THE WATER RISER THAT BOTH LAVATORIES |
| ARE SUPPLIED WITH HOT OR TEMPERED WATER, LIMITED TO 110 |
| DEGREES IN ACCORDANCE WITH THE 2014 FBC-PLUMBING |
| SEC.607.1, 607.1.1, 607.1.2. |
| 3) SHOW THE NEW LAVATORY IN THE NEW ACCESSIBLE TOILET |
| ROOM ON THE SANITARY RISER. |
| 4) THE SANITARY SHOWS A FLAT DRY VENT WHICH IS NOT |
| PERMITTED PER THE PLUMBING CODE. THE VENT SHALL CONNECT |
| TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE |
| HORIZONTAL DRAIN PIPE. 2014 FBCP SEC.905.3. |
| 5) SHT. A100 - THE TYPICAL HANDICAP RESTROOM DETAIL |
| SHOWS THE MINIMUM INSIDE DIMENSION AS 7'-6" AND THE |
| PLAN VIEW SHOWS THE RESTROOM AS 7'-8" FROM THE INSIDE |
| FACE OF THE WALL TO THE OUTSIDE FACE OF THE WALL AS |
| 7'-8". CLARIFY. SHOW THE THE INSIDE CLEAR DIMENSIONS OF |
| THE ACCESSIBLE TOILET ROOMS.THE MINIMUM WIDTH WHEN THE |
| THE PLUMBING FIXTURES ARE ON THE SAME WALL IS 85 |
| INCHES.86 INCHES ALLOWS FOR TOLERANCE. |
| 6) THE MANUF. SPECS/INSTALLATION MANUAL FOR THE |
| TANKLESS WATER HEATER SHALL BE ONSITE FOR THE |
| INSPECTOR. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |