Plan Review Notes For Permit 16010623 |
Permit Number |
16010623 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-01 14:46:13 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010623 | | 2/1/16 | | | | 1) PROVIDE TOILET EXHAUST FAN SCHEDULES. | | 2) PROVIDE TOILET ROOM EXHAUST VENTILATION PLANS THAT | | INCLUDE THE THE TYPES AND SIZES OF EXHAUST FAN DUCTS, | | THE DUCT RUNS, AND TERMINATION LOCATIONS. | | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | PROPOSED TENANT SPACES. SHOW THE REQUIRED AND PROVIDED | | CFM'S OF OUTDOOR AIR. | | 4) ENERGY COMPLIANCE IS REQUIRED IN ACCORDANCE WITH | | SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. SEE THE | | DEFINITION OF RENOVATED BUILDING- SECTION 202. PLEASE | | NOTE THE NEW EXTERIOR DOORS MUST MEET OR EXCEED THE | | CURRENT EFFICIENCY RATINGS ACCORDING TO THE CODE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|