2016-02-11 10:13:30 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW |
| VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND |
| DATA. A NOTE WILL SUFFICE. |
| 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL |
| SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING |
| SHOWN FOR THIS PROJECT. PER NEC 230.2 SPECIAL |
| PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING. |
| COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE |
| SHOWN. |
| 3. SEE MECHANICAL COMMENTS REGARDING EQUIPMENT FOR A |
| COMPLETE REVIEW. |
| 4. PLEASE REVIEW DEMAND LOADS TO BE IN COMPLIANCE WITH |
| NEC 220 REQUIREMENTS, PROVIDE A COMPLETE CALCULATION. |
| 5. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT |
| INFORMATION: FOR EXAMPLE, AIC RATING ETC. FBC 107. |
| 6. ID THE FLOOR PLAN WITH CIRCUIT DESIGNATION. FBC 107. |
| 7. PROVIDE SPEC SHEETS FOR INSTANT- HOT WH SELECTED TO |
| VERIFY LOADS, FBC 107 |
| 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| THIS PROJECT. |
| |