2016-01-21 12:33:111) THE GAS TABLE REFERENCED ON THE PLAN FOR THE CSST
 (402.4 (13) ) IS FOR SEMIRIDGID COPPER TUBING IN THE
 GAS CODE. CLARIFY
 2) THE GAS TABLE REFERENCED ON THE PLAN FOR THE PE PIPE
 (402.4 (19) ) IS FOR CSST IN THE GAS CODE.CLARIFY.
 3) PER TABLE 402.4 (21), THE MAXIMUM BTU LOAD ON A 0.5
 PSI 3/4" PE LINE AT 30 FT. IS 222,000 BTU'S. THE 3/4"
 PE LINE COMING FROM THE METER NEEDS TO BE INCREASED TO
 1".
  