Plan Review Notes For Permit 16010556 |
Permit Number |
16010556 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-07-28 15:54:44 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | -PROFFESIONAL ENGINEER JOHN HOLT LICENSE HAS BEEN | | SUSPENDED BY THE BOARD, HIS SIGNATURE IS NO LONGER | | VALID. NEW DESIGNER IS REQUIRED | | | | THESE COMMENTS WERE NOT ADDRESSED ( 2ND REQUEST ) | | | | 1) A 20 AMP DEDICATED BRANCH CIRCUIT IS REQUIRED PER | | NEC 600.5. IF EXISTING PLEASE MARK ON PLANS ! | | | | 2) ADD A NOTE FOR FBC-E SECTION C405.2.4 EXTERIOR | | LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN | | ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. |
|