Plan Review Notes
Plan Review Notes For Permit 16010556
Permit Number 16010556
Review Stop E
Sequence Number 2
Notes
Date Text
2016-07-28 15:54:44REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 -PROFFESIONAL ENGINEER JOHN HOLT LICENSE HAS BEEN
 SUSPENDED BY THE BOARD, HIS SIGNATURE IS NO LONGER
 VALID. NEW DESIGNER IS REQUIRED
  
 THESE COMMENTS WERE NOT ADDRESSED ( 2ND REQUEST )
  
 1) A 20 AMP DEDICATED BRANCH CIRCUIT IS REQUIRED PER
 NEC 600.5. IF EXISTING PLEASE MARK ON PLANS !
  
 2) ADD A NOTE FOR FBC-E SECTION C405.2.4 EXTERIOR
 LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.