2016-02-04 09:41:59 | APPROIVED THE APPLICATION BUT MADE A NOTE FOR THE | | INSPECTOR: NOTICE TO INSPECTOR: | | VERIFY SERVICE CONDUCTOR SIZING AS #2 AWG IS ONLY RATED | | FOR 115 AMP AND APPEARS TO BE PROTECTED WITH BY 150 AMP | | OCPD. WORK PERMITTED UNDER PERMIT 14020436. | | |
|