Plan Review Notes
Plan Review Notes For Permit 16010499
Permit Number 16010499
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-27 18:40:58THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. CITY OF WEST PALM BEACH AMENDMENTS REQUIRES THAT THE
 ALL DRAWINGS BEAR NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 2. PER NEC 250.66 THE MINIMUM GEC FOR #1 COPPER IS #6
 CU. CORRECT YOUR DRAWING ACCORDINGLY.
 3. NEC 250.94 REQUIRES THAT YOUR PROVIDE AN
 INTER-SYSTEM BONDING TERMINAL.
 4. YOU SHALL SUBMIT ACTUAL LOAD CALCS NOT SIMPLY THE
 RESULTS OF ONE.
 5. FBC-R314 REQUIRES THAT YOU COME INTO SMOKE DETECTOR
 COMPLIANCE.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  