2016-01-21 07:33:18 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010471 | | 01/21/16 | | | | 1) AC PLANS: A) PLACE A NORTH DIRECTIONAL ARROW ON THE | | PLAN FOR PROPER REVIEW OF THE AC CALCULATIONS. B) | | PROVIDE THE SUPPLY CFM'S ATR EACH DIFFUSER, AND RETURN | | CFM'S AT EACH GRILL. C) PROVIDE THE SENSIBLE AND LATENT | | CAPACITIES OF THE AC SYSTEMS TO VERIFY COMPLIANCE WITH | | THE CALCULATIONS (EQUIPMENT MAKE AND MODEL SELECTIONS | | BETWEEN CALCS AND PLAN DO NOT MATCH). | | 2) PROVIDE AC CALCULATIONS BASED ON THE CORRECT DESIGN | | TEMPERATURES FOR WEST PALM BEACH- THE DRYBULB | | TEMPERATURES ON THE SUBMITTED CALCS ARE INCORRECT. | | 3) PROVIDE DETAILS FOR PRIMARY AND SECONDARY CONDENSATE | | DISPOSAL. | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN | | EXHAUST HOOD AND THE APPLIANCE IT IS VENTING. | | 5) CLARIFY IF THE ELECTRICAL TO POWER THE AC SYSTEMS IS | | TO BE INCLUDED AS A SUB-PERMIT OF THIS APPLICATION, OR | | TO BE DONE UNDER A SEPARATE PERMIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|