Plan Review Notes
Plan Review Notes For Permit 16010466
Permit Number 16010466
Review Stop M
Sequence Number 3
Notes
Date Text
2016-04-28 09:00:183RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010466
 4/28/16
  
 1) SHEET M-1: THE MODEL NUMBERS FOR THE NEW 3-TON BARD
 UNIT SHOWN ON THE PLAN DO NOT MATCH THE NUMBERS SHOWN
 ON THE NEW SUBMITTAL- PLEASE CORRECT.
 2) M-1: THE AC SCHEDULE INDICATES 2600 CFM'S OF SUPPLY
 AIR FOR THE 3-TON SYSTEM WHICH WOULLD NOT BE POSSIBLE
 FOR A 3-TON SYSTYEM. PLEASE NOTE THE NEW BARD SPECS
 INDICATE THE UNIT WILL PRODUCE 1100 CFRMS.
 3) THE SUBMITTED PRODUCT APPROVAL FOR THE LOUVER IS
 INCOMPLETE: PLEASE PROVIDE A COMPLETE DOCUMENT THAT
 INCLUDES THE INSTALLATION INSTRUCTIONS AND
 CERTIFICATION CERTIFICATE AS SHOWN ON PAGE-3 OF THE
 SUBMITTAL.
 4) PROVIDE AN NOA OR FLORIDA PRODUCT APPROVAL FOR THE
 GREENHECK FAN EXTERIOR WEATHERHEAD.
 5) ADVISORY: AS REQUESTED BY THE CONTRACTOR, THE WIND
 LOAD ENGINEERING FOR INSTALLATION OF THE BARD UNIT CAN
 BE DONE AS A DEFERRED SUBMITTAL. PLEASE REVIEW SECTION
 107.3.4.2 WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE:1) DEFERRED SUBMITTAL: FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  