Plan Review Notes For Permit 16010466
Permit Number 16010466
Review Stop E
Sequence Number 2
Notes
Date Text
2016-04-05 07:23:402ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 PROVISO TO BE PROVIDED ON AS- BUILTS
  
 3. SHOW THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 AT THE SERVICE. NEC 250.66
 5. CLARIFY THE REDUCTION OF THE NEUTRAL CONDUCTOR AT
 THE SERVICE. NEC 250.61C. PROVIDE A NEUTRAL CALCULATION
 OR CLARIFY.
  
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II