2016-01-25 17:49:14 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16010466 | | 1/25/16 | | | | 1) CLARIFY HOW THE AC SYSTEM WAS SIZED, AND INDICATE | | HOW IT WILL FUNCTION- WILL IT BE CONTROLLED BY A | | THERMOSTAT? | | 2) PROVIDE THE WIND LOAD DESIGN CRITERIA AND DETAILS | | FOR ATTACHMENT OF THE AC UNIT TO THE STRUCTURE- SECTION | | 301.15 FBC-14 MECHANICAL. | | 3) SHEET S-4: A NEW SUPPLY FAN IS SHOWN ON S-3, AND TWO | | EXHAUST FANS ARE SHOWN ON E-3. PLEASE PROVIDE EQUIPMENT | | SCHEDULES FOR THE FANS, AND CLARIFY HOW THE SYSTEMS | | WERE SIZED. | | 4) PROVIDE FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S | | FOR THE INTAKE AND EXHAUST LOUVERS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|