2016-01-25 17:49:141ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010466
 1/25/16
  
 1) CLARIFY HOW THE AC SYSTEM WAS SIZED, AND INDICATE
 HOW IT WILL FUNCTION- WILL IT BE CONTROLLED BY A
 THERMOSTAT?
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA AND DETAILS
 FOR ATTACHMENT OF THE AC UNIT TO THE STRUCTURE- SECTION
 301.15 FBC-14 MECHANICAL.
 3) SHEET S-4: A NEW SUPPLY FAN IS SHOWN ON S-3, AND TWO
 EXHAUST FANS ARE SHOWN ON E-3. PLEASE PROVIDE EQUIPMENT
 SCHEDULES FOR THE FANS, AND CLARIFY HOW THE SYSTEMS
 WERE SIZED.
 4) PROVIDE FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S
 FOR THE INTAKE AND EXHAUST LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  