2016-02-03 07:57:51 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 1601046 |
| ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT |
| STATION ADDITION & RENOVATION |
| BLDG. RISK CATEGORY: IV/ 180 VULT/ MPH |
| CONT: FLORIDA DESIGN DRILLING CORP. |
| TEL: 561-844-2966 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 03/ 2016 |
| ACTION: DENIED |
| |
| 1) THIS REVIEW NO SURVEY WAS SUBMITTED, IT APPEARS THIS |
| STURTURE IS LOCATED IN A A5 FLOOD ZONE, FBC BUILDING |
| 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 1A) 2014 FBC-B 1612.1 WITHIN FLOOD HAZARD AREAS AS |
| ESTABLISHED IN SECTION 1612.3, ALL NEW CONSTRUCTION OF |
| BUILDINGS, STRUCTURES AND PORTIONS OF BUILDINGS AND |
| STRUCTURES, INCLUDING SUBSTANTIAL IMPROVEMENT AND |
| RESTORATION OF SUBSTANTIAL DAMAGE TO BUILDINGS AND |
| STRUCTURES, SHALL BE DESIGNED AND CONSTRUCTED TO RESIST |
| THE EFFECTS OF FLOOD HAZARDS AND FLOOD LOADS. |
| |
| 1612.4 DESIGN AND CONSTRUCTION. THE DESIGN AND |
| CONSTRUCTION OF BUILDINGS AND STRUCTURES LOCATED IN |
| FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH HAZARD |
| AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7 |
| AND WITH ASCE 24. |
| |
| 1B) SHEET S-3 THE NEW ADDITION SHOWS THE 100 YEAR BASE |
| FLOOD AT 7.0 FT. NGVD AND THE FINISH FLOOR AT ELEVATION |
| 7.5 FT. NGVD IN ACCORDANCE WITH THE CITY MUNI CODE |
| 94-546 (B)(2) FOR NON-RESIDENTIAL BUILDINGS. PLEASE |
| NOTE THIS ORDANCE WAS WRITTEN FOR COMMERCIAL BUILDINGS |
| WITH A RISK CATEGORY II TYPE STRUCTURES. ASCE 24-05 |
| UNDER THE HEADING 2.3 TABLE 2-1 FOR RISK CATEGORY IV |
| STURCTURES REQUIRES BFE + 2 FT. OR DFE WHICHEVER IS |
| HIGHER. |
| |
| 1C) THE NEW ADDITION HAS WITH FINISH FLOOR AT 7.5 NGVD |
| AND THE EXISTING BUILDING (SHEET C-2 & C-3) SHOW FINISH |
| FLOOR AT 4.99 NGVD. THE AREAS OF BOTH THE NEW ADDITION |
| AND THE EXISTING BUILDING UNDER GOING SUBSTANTIAL |
| IMPROVEMENT WILL NEED TO COMPLY WITH ASCE 24-05 TABLE |
| 6-1 DRY FLOODPROOFING FOR BUILDINGS RISK CATEGORY IV |
| BFE + 2 FT. OR DFE WHICHEVER IS GREATER, AND ALL OF THE |
| DRYFLOODPROOFING REQUIREMENTS FOUND IN ASCE 24-05 |
| SECTION 6.2.2 DRY FLOODPROOFING REQUIREMENTS, ALSO |
| REVIEW FEMA'S TECHNICAL BULLETIN 3-93 NON-RESIDENTIAL |
| REQUIREMENTS AND CERTIFICATIONS. THESE DOCUMENTS ARE |
| OVER AND ABOVE THE FLOOD ELEVATION CERTIFICATE. |
| |
| 1D) 2014 FBC-B 1403.6 FLOOD RESISTANCE. FOR BUILDINGS |
| IN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION 1612.3, |
| EXTERIOR WALLS EXTENDING BELOW THE ELEVATION REQUIRED |
| BY SECTION 1612 SHALL BE CONSTRUCTED WITH |
| FLOOD-DAMAGE-RESISTANT MATERIALS. WOOD SHALL BE |
| PRESSURE-PRESERVATIVE TREATED IN ACCORDANCE WITH AWPA |
| U1 FOR THE SPECIES, PRODUCT AND END USE USING A |
| PRESERVATIVE LISTED IN SECTION 4 OF AWPA U1 OR |
| DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK LOCUST OR |
| CEDAR. |
| |
| 1E) 2014 FBC-B 1403.7 FLOOD RESISTANCE FOR COASTAL HIGH |
| HAZARD AREAS. FOR BUILDINGS IN COASTAL HIGH HAZARD |
| AREAS AS ESTABLISHED IN SECTION 1612.3, ELECTRICAL, |
| MECHANICAL AND PLUMBING SYSTEM COMPONENTS SHALL NOT BE |
| MOUNTED ON OR PENETRATE THROUGH EXTERIOR WALLS THAT ARE |
| DESIGNED TO BREAK AWAY UNDER FLOOD LOADS. |
| |
| 1F) 2014 FBC-EXISTING DLDG. CODE 1103.5 FLOOD HAZARD |
| AREAS. ADDITIONS AND FOUNDATIONS IN FLOOD HAZARD AREAS |
| SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: |
| 1-5. |
| |
| 2) SHEET S-1 NOTE # 1 SLAB ON GRADE INDICATES SEE SOILS |
| REPORT. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE |
| THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE |
| SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR |
| TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| FBC-B1804.4 GRADING AND FILL IN FLOOD HAZARD AREAS. IN |
| FLOOD HAZARD AREAS ESTABLISHED IN SECTION 1612.3, |
| GRADING AND/OR FILL SHALL NOT BE APPROVED: |
| FBC-B 1804.6 CONTROLLED LOW-STRENGTH MATERIAL (CLSM). |
| WHERE SHALLOW FOUNDATIONS WILL BEAR ON CONTROLLED |
| LOW-STRENGTH MATERIAL (CLSM), THE CLSM SHALL COMPLY |
| WITH THE PROVISIONS OF AN APPROVED GEOTECHNICAL REPORT, |
| AS SET FORTH IN SECTION 1803. |
| |
| 3) SHEET S-7INDICATES THE HANDRAIL AT AN ELEVATION OF |
| 39 INCHES MEASURED ABOVE STAIR TREAD NOSINGS, OR FINISH |
| SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT LESS THAN |
| 34 INCHES (864 MM) AND NOT MORE THAN 38 INCHES (965 |
| MM). |
| |
| 4) SHEET S-7 ALSO INDICATES THE USE OF A GUARDRAIL 42 |
| INCHES IN HEIGHT. PLEASE GIVE THE DIMENSION FOR THE MID |
| RAIL TO SHOW COMPLIANCE WITH 2014 FBC-B |
| 1013.4 IT APPEARS THEY ARE TAKING EXCEPTION# 3. |
| |
| 5) SHEET S-1 SHOWS ROOF ZONES 3-6 AND ASSOCIATED |
| PRESSURES. FOR COMPONENTS AND CLADDING USING ASCE 7-10 |
| FIGURE 30.5.1 METHOD 1 ENCLOSED BUILDING LESS THAN 60 |
| FEET IN HEIGHT , THERE ARE ONLY 3 ROOF ZONES 1-3 AND |
| WALL ZONES 4 & 5. PLEASE EXPLAIN ROOF ZONES 4, 5 & 6? |
| ADDITIONAL INFORMATION, PLEASE ALSO INDICATE IF THESE |
| PRESSURES ARE VALY OR VASD PRESSURES. |
| |
| 6) NO PRODUCT APPROVALS WERE SUBMITTED THIS REVIEW, |
| SUBMIT (2) OF EACH APPROVAL TYPE. PLEASE PROVIDE |
| COMPLIANCE WITH 2014 FBC-B 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (C) PANEL WALLS: WALL LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 7) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 8) THE MECHANICAL SHEET M-1 SHOWS AN A/C UNIT MOUNTED |
| ON THE EXTERIOR SIDE OF THE WALL. PLEASE SHOW |
| COMPLIANCE WITH ASCE 24-05. IN COASTAL A ZONES AND WHEN |
| LOCATED ON THE EXTERIOR OF THE STRUCTURE, MECHANICAL OR |
| A/C EQUIPMENT AND SYSTEMS SHALL BE LOCATED ON THE |
| LANDWARD SIDE OF THE STRUCTUREABOVE THE ELEVATION IN |
| TABLE 7-1. BUILDING RISK CATEGORY IV BFE +2FT. OR DFE |
| WHICHEVER IS HIGHER. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |