2016-03-23 09:21:27SPOKE W/GLEN SPINA OFFICES AND THEY WILL SEND ME AN
 EMAIL ACKNOWLEDGING MY REQUIREMENTS. ONCE RECEIVED I
 WILL APPROVE THE ELECTRICAL REVIEW WITH A PROVISO
 REQUIRING DAYLIGHT ZONE CONTROL IN THESE UNITS.
2016-03-22 14:43:07ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED, BUT I MAY HAVE OVERSEEN THE
 TWO NEW COMMENTS ON THE LIGHTING PAGE AS MENTIONED
 BELOW.
  
 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #:16010446
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E2.1
 1. ROOMS 311, 314 & 318 DO NOT COMPLY WITH THE
 FBC-C405.2.2.3 DAYLIGHT ZONE CONTROLS. PLEASE SEPARATE
 FIXTURE SWITCHING TO COMPLY.
 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  