2016-03-23 09:21:27 | SPOKE W/GLEN SPINA OFFICES AND THEY WILL SEND ME AN |
| EMAIL ACKNOWLEDGING MY REQUIREMENTS. ONCE RECEIVED I |
| WILL APPROVE THE ELECTRICAL REVIEW WITH A PROVISO |
| REQUIRING DAYLIGHT ZONE CONTROL IN THESE UNITS. |
2016-03-22 14:43:07 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN |
| SATISFACTORILY ADDRESSED, BUT I MAY HAVE OVERSEEN THE |
| TWO NEW COMMENTS ON THE LIGHTING PAGE AS MENTIONED |
| BELOW. |
| |
| 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #:16010446 |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| SHEET E2.1 |
| 1. ROOMS 311, 314 & 318 DO NOT COMPLY WITH THE |
| FBC-C405.2.2.3 DAYLIGHT ZONE CONTROLS. PLEASE SEPARATE |
| FIXTURE SWITCHING TO COMPLY. |
| 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED & UNCONDITIONED SPACES. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |