Plan Review Notes
Plan Review Notes For Permit 16010446
Permit Number 16010446
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-04 16:42:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010446
 2/4/16
  
 1) THE NEW VAV-1 BOX MUST BE EQUIPPED WITH HEAT UNLESS
 IT IS BEING PROVIDED BY ANOTHER SOURCE- SEE SECTION
 309.1.
 2) FIRE DAMPERS APPEAR TO BE MISSING FOR THE DUCTS
 PENETRATING THROUGH THE RATED CORRIDOR/WORK STATIONS
 ROOM WALL.
 3) PROVIDE AN INSTALLATION DETAIL FOR THE NEW VAV.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  