Plan Review Notes
Plan Review Notes For Permit 16010446
Permit Number 16010446
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-01-20 16:15:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 2. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 3. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  