Plan Review Notes For Permit 16010446 |
Permit Number |
16010446 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-20 16:15:36 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF | | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE | | AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF | | WALLS REQUIRE AN EVALUATION. | | | | 2. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | 3. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|